直流電網(wǎng)絕緣監(jiān)測儀

image.png

技術(shù)參數(shù)Technical parameters 

監(jiān)測直流電網(wǎng)的絕緣電阻。

Monitoring the insulation resistance at the DC network system .

當(dāng)電網(wǎng)絕緣電阻低于設(shè)定值時,延時≤1秒輸出一報警信號;When the power grid insulation resistance is lower than the set value, delay ≤1 second and output an alarm signal.

網(wǎng)絡(luò)工作電壓Network working voltage: 24VDC,100VDC,220VDC。

工作電壓容差Operating voltage tolerance: ±20%。

指示精度 Accuracy of indication:⑩(或按弧張Or arc length:±1.5%)。

環(huán)境溫度 Ambient temperature range:-25℃ to +55℃。

外殼防護(hù) Housing protection:IP44。

耐振動 Vibration resistance:2-100HZ≤0.7g。

耐電壓 Dielectric test:AC2.6KV,50HZ,1min。

輸出觸點容量 Contact rating:AC250V,3A;DC28V,3A。

電源功耗 Power consumption:≤2VA。

安裝方式:面板嵌入式,垂直(⊥)安裝 Panel embedded, vertical (⊥) installation.

產(chǎn)品分類 Kind of products

型號

Type

展開角

angle

外形尺寸(mm

OutlineAXBXC

開孔尺寸

Cut-outmm

結(jié)構(gòu)代碼

Structure   code

外形圖

Outline   drawing

接線圖

Wiring   drawing

重量(Kg

Weight

F72-ZBKΩ,AH72-ZBKΩ

90°

240°

72X72X120

68+0.5X68+0.5

A/B

Figure 1/2

Figure  4

0.5/0.65

F96-ZBKΩ,AH96-ZBKΩ

96X96X102

92+0.5X92+0.5

A/B

Figure 1/2

Figure  3

0.6/0.75

規(guī)格表 Measuring range

測量范圍

Measuring   range

中心值

Central   value

報警設(shè)定值

Alarm   setting value(±20%)

電壓規(guī)格

Voltage   specification

備注

Note

0-200-5000KΩ

200KΩ

10KΩ

30KΩ

60KΩ

100KΩ

200KΩ

300KΩ

500KΩ

1000KΩ

DC24V;(DC220V)

常規(guī)routine

0-20-500KΩ

20KΩ

1KΩ

3KΩ

6KΩ

10KΩ

20KΩ

30KΩ

50KΩ

100KΩ

DC24V

定制

custom

0-2-50KΩ

2KΩ

0.1K

0.3K

0.6K

1KΩ

2KΩ

3KΩ

5KΩ

10KΩ

DC24V

0-100-1000KΩ

100KΩ

10KΩ

30KΩ

60KΩ

100KΩ





DC24V(DC220V)

0-0.2-5MΩ

0.2MΩ

0.01M

0.03M

0.06M

0.1MΩ

0.2MΩ

0.3MΩ

0.5MΩ

1MΩ

DC24V;(DC220V)


 外形圖 Outline drawing

image.png

刻度盤Dial 

1.jpg

背部圖/接線圖 Back figure/Wiring diagram

image.png

使用說明書Directions for use 

儀表正確連接后,接通電源到額定電壓,此時綠色指示燈亮,儀表即處于監(jiān)測狀態(tài),指針指示值即為電網(wǎng)絕緣電阻值(自檢檔除外)。After the instrument is correctly connected, connect the power supply to the rated voltage, and the green indicator light will be on at this time, the instrument will be in the monitoring state, and the indicator value is the insulation resistance value of the power grid (excluding the self check file).

儀表在工作時報警設(shè)定開關(guān)應(yīng)設(shè)置在所選定的報警值位置,具體報警值檔位見背面展示圖。用戶有其他要求時可在訂貨時注明。When the instrument is working, the alarm setting switch shall be set at the selected alarm value position. See the back display diagram for the specific alarm value position. Other requirements of users can be noted when ordering.

如需判別儀表工作是否正常時可進(jìn)行自檢,將儀表后面開關(guān)設(shè)置在自檢檔位,儀表即進(jìn)行自檢,儀表能進(jìn)行正常自檢時指針應(yīng)指示在10KΩ位置,同時報警紅燈點亮,報警輸出端有輸出。自檢完畢后必須將儀表恢復(fù)到正常報警檔位上。If it is necessary to judge whether the instrument works normally, self inspection can be carried out. Set the switch at the back of the instrument to the self inspection gear, and the instrument will carry out self inspection. When the instrument can carry out normal self inspection, the pointer shall indicate the position of 10KΩ, and the alarm red light will be on, and the alarm output terminal has output. After the self-test, the instrument must be restored to the normal alarm gear.