技術參數Technical parameters
監測直流電網的絕緣電阻。
Monitoring the insulation resistance at the DC network system .
當電網絕緣電阻低于設定值時,延時≤1秒輸出一報警信號;When the power grid insulation resistance is lower than the set value, delay ≤1 second and output an alarm signal.
網絡工作電壓Network working voltage: 24VDC,100VDC,220VDC。
工作電壓容差Operating voltage tolerance: ±20%。
指示精度 Accuracy of indication:⑩(或按弧張Or arc length:±1.5%)。
環境溫度 Ambient temperature range:-25℃ to +55℃。
外殼防護 Housing protection:IP44。
耐振動 Vibration resistance:2-100HZ≤0.7g。
耐電壓 Dielectric test:AC2.6KV,50HZ,1min。
輸出觸點容量 Contact rating:AC250V,3A;DC28V,3A。
電源功耗 Power consumption:≤2VA。
安裝方式:面板嵌入式,垂直(⊥)安裝 Panel embedded, vertical (⊥) installation.
產品分類 Kind of products
型號 Type | 展開角 angle | 外形尺寸(mm) Outline(AXBXC) | 開孔尺寸 Cut-out(mm) | 結構代碼 Structure code | 外形圖 Outline drawing | 接線圖 Wiring drawing | 重量(Kg) Weight |
Q72-MΩB,61C14G-MΩ | 90° | 72X72X120 | 68+0.5X68+0.5 | A | 圖Figure 1 | 圖Figure 4 | 0.5 |
Q72-ZMΩB,61C14-MΩ | 240° | 72X72X120 | 68+0.5X68+0.5 | B | 圖Figure 2 | 圖Figure 4 | 0.65 |
Q96-MΩB,51C5G-MΩ | 90° | 96X96X102 | 92+0.5X92+0.5 | A | 圖Figure 1 | 圖Figure 3 | 0.6 |
Q96-ZMΩB,51C5-MΩ | 240° | 96X96X102 | 92+0.5X92+0.5 | B | 圖Figure 2 | 圖Figure 3 | 0.75 |
規格表 Measuring range
測量范圍 Measuring range | 中心值 Central value | 報警設定值 Alarm setting value(±20%) | 電壓規格 Voltage specification | 備注 Note | |||||||
0-0.2-5MΩ | 0.2MΩ | 0.01M | 0.03M | 0.06M | 0.1MΩ | 0.2MΩ | 0.3MΩ | 0.5MΩ | 1MΩ | DC24V;(DC220V) | 常規routine |
外形圖 Outline drawing
背部圖/接線圖 Back figure/Wiring
使用說明書Directions for use
儀表正確連接后,接通電源到額定電壓,此時綠色指示燈亮,儀表即處于監測狀態,指針指示值即為電網絕緣電阻值(自檢檔除外)。After the instrument is correctly connected, connect the power supply to the rated voltage, and the green indicator light will be on at this time, the instrument will be in the monitoring state, and the indicator value is the insulation resistance value of the power grid (excluding the self check file).
儀表在工作時報警設定開關應設置在所選定的報警值位置,具體報警值檔位見背面展示圖。用戶有其他要求時可在訂貨時注明。When the instrument is working, the alarm setting switch shall be set at the selected alarm value position. See the back display diagram for the specific alarm value position. Other requirements of users can be noted when ordering.如需判別儀表工作是否正常時可進行自檢,將儀表后面開關設置在自檢檔位,儀表即進行自檢,儀表能進行正常自檢時指針應指示在10KΩ位置,同時報警紅燈點亮,報警輸出端有輸出。自檢完畢后必須將儀表恢復到正常報警檔位上。If it is necessary to judge whether the instrument works normally, self inspection can be carried out. Set the switch at the back of the instrument to the self inspection gear, and the instrument will carry out self inspection. When the instrument can carry out normal self inspection, the pointer shall indicate the position of 10KΩ, and the alarm red light will be on, and the alarm output terminal has output. After the self-test, the instrument must be restored to the normal alarm gear.